Features
- Single phase (C & D series)
- 9999 free range is our standard display
range.
- In case you change the meter from panel, no
need to uninstall wire / cable / bracket / case from the panel or machine.
Simply set apart the PCB part by pulling out the front cover.
- No need jumper. Display value and decimal
point position programmable by buttons.
Example) In need to display 0~6600V while input signal is 0~220V (DV-232) ->
The display value can be calibrated in "LO-SE" and "HI-SE"
mode. If the meter input range is 0~220V, the factory setting display value is
0~220V while the input 0~220V unless changed. If you need to display 0~6600V
while the meter input range 0~220V, set "LO-SE" as '0' and
"HI-SE" as '6600' then, the meter will display 0~6600V while the
input signal 0~220V.
- If the display value needs adjustment while
installation and connection, it can be done by using buttons.
Example) If the meter indicates "303.0" while the input signal is
"300.0", set this discrepancy value "-003.0" at Adjustment
mode. Then, the meter will show "300.0"
- Flashing 'H-Er' at over 120% input range.
For example, in case of 0~400VAC input range meter, the meter measures by
480VAC. At over 480VAC, the meter shows 'H-Er' message.
- All meters have temperature compensation
function built in, so the meter operates correctly within the working
temperature.
- Various output option supportable such as
Analogue 4-20mA, High & Low relays, RS485 and, RS232C. In case of Analogue
4-20mA output, the load resistance maximum is 1K¥Ø, so it'll let you save the engineering cost.
- Multi-drop maximum is 255 in case of RS485.
- DIN
mounting : 96 x 48mm
- Case : Non-flammable ABS
- CE certified.
|