 HYUNDAI 
                        HGM400 Molded 
                        Case Circuit Breaker (MCCB)
 
  | General 
                                    Specifications |  
  | Rated Insulation Voltage, Ui | 1,000 V | Suitability for Isolation | Yes |  
  | Rated Operational Voltage, Ue | 690 V | Utilization Category | A |  
  | Impulse Withstand Voltage, Uimp | 8 kV | Pollution Degree | 3 |  
  | Protective Function | Overload, short-circuit and instantaneous protection | Reference Standard | IEC 60947-2 |    
 
  | Model | HGM400 |  
  | Frame (AF) | 400 |  
  | Pole (P) | 2, 3, 4 |  
  | Rated
  current, at 40 ℃ (A) | 250, 300, 350, 400 |  
  | Rated 
                                    short-circuit
                                     breaking 
                                    capacity
                                      [Icu] 
                                    (kA rms) | Recognition code for order | HGM400E | HGM400S | HGM400H | HGM400L |  
  | AC660/690 V | 5 | 8 | 10 | 14 |  
  | AC480/500 V | 18 | 35 | 50 | 65 |  
  | AC440/460 V | 38 | 50 | 70 | 85 |  
  | AC380/415 V | 45 | 65 | 85 | 100 |  
  | AC220/240 V | 50 | 75 | 100 | 125 |  
  | DC250 V (2P) | 20 | 25 | 40 | 40 |  
  | Service
  breaking capacity [Ics = % Icu] | 100 |  
  | Endurance
                                     (Durability) | Mechanical | 4,000 |  
  | Electrical | 1,000 |  
  | Trip Device
                                     Thermal 
                                    magnetic | Long time
                                     [LT] | Fixed | (1.0) x In |  
  | Adjustable | (0.63 - 0.8 - 1.0) x In |  
  | Instantaneous [INST] | 10 x In |  |  |